Three-phase model of a 380 kV overhead transmission line for measuring steady-state operating conditions (no-load, matching, short-circuit) with the following specifications:
- Quad bundle 240/40,
- with surge impedance 240 Ohm and
- natural power 600 MW
- length 360 km.
- Tappings enable the carrying out of investigations at lengths of 144 km resp. 216 km.
- Scale factor: 1/1000 for current and voltage.
- Length: 360 km 216 km 144 km
- Ohmic resistance: 13 Ohm 8 Ohm 5 Ohm
- Inductance: 290 mH 174 mH 116 mH
- Oper. capacity: 5 µF 3 µF 2 µF